System Sensor 5604 is a single-circuit mechanical heat detector with a 194°F (90°C) fixed temperature rating, part of the 5600 Series. System Sensor offers the 5600 Series as a low-cost means of property protection against fire and for non-life-safety installations where smoke detectors are inappropriate.The fixed temperature element uses a metal contact held by a fusible alloy; when the alloy melts at the rated temperature the contact closes the circuit. The circular external heat collector then drops from the detector to show which unit is in alarm. The housing is marked FX and 194°F/90°C so the model can be identified after installation.Specifications Type Mechanical heat detector, single circuit, normally open Activation Fixed temperature Alarm temperature 194°F (90°C) Max. installation temperature 150°F (65.6°C) UL protected spacing 25 x 25 ft (7.62 x 7.62 m) at 10 ft ceiling Contact ratings 6-125 VAC / 3 A; 6-28 VDC / 1 A; 125 VDC / 0.3 A; 250 VDC / 0.1 A Input terminals 14-22 AWG Humidity 5 to 95% RH, non-condensing Dimensions 4.57 in. diameter x 1.69 in. high with bracket Weight 6 oz (170 g) Standard UL 521 Installation notes Fixed temperature models (5603, 5604, 5623 and 5624) are non-resettable and cannot be tested. Shipping and storage temperature must not exceed 122°F (50°C), to avoid activating the fixed temperature element. The reversible mounting bracket fits 3-1/2 in. and 4 in. octagonal boxes, single-gang boxes, and 4 in. square boxes with a square-to-round plaster ring, for flush or surface mounting. Refer to NFPA 72 for spacing reductions when the ceiling is higher than 10 ft. Related models 5603 — single circuit, 135°F fixed temperature. 5602 — single circuit, 194°F fixed temperature/rate-of-rise. 5624 — dual circuit, 194°F fixed temperature. 5601P and 5622 — 135°F and 194°F fixed temperature/rate-of-rise models. Documents 5600 Series Mechanical Heat Detectors — Data Sheet (PDF) 5600 Series Installation Instructions (PDF) FAQCan the 5604 be reset or tested?No. Fixed temperature models such as the 5604 are non-resettable and cannot be tested. Only the rate-of-rise element of the combination models is self-restoring.What spacing does the 5604 cover?UL protected spacing is 25 x 25 ft (7.62 x 7.62 m) on a 10 ft ceiling. Refer to NFPA 72 for reductions on higher ceilings.What is the highest ambient temperature for installation?150°F (65.6°C). Shipping and storage temperature must not exceed 122°F (50°C).Is there a dual-circuit or rate-of-rise version?Yes. The 5624 is the dual-circuit 194°F fixed temperature model, and the 5602 adds rate-of-rise to a 194°F single-circuit detector.